Finding Shorts in Electrical Wiring Circuits: Earth Faults in Radial Circuits
Key Definitions
- Short Circuit: Low resistance path between line and neutral, or between phases in a three-phase system.
- Earth Fault: Low resistance path between line and Earth (or CPC) or between phase and Earth in a three-phase system.
- CPC (Circuit Protective Conductor): The earth conductor in a twin and earth cable.
Testing in a Healthy Circuit
- Circuit: Radial cooker circuit, 6mm² by 2.5mm² twin and earth cable, circuit length of 90m in one direction.
- Challenge: Test meter probes have a lead length of 1m, insufficient for directly measuring conductors.
Measurement Strategy
- Use a Wago connector at the point of use (e.g., cooker) as a return path.
- Measurements:
- Line to Neutral: 0.12 ohms
- Line to CPC: 0.2 ohms
- Neutral to CPC: 0.2 ohms
- Tables for Verification: Use Table B1 in Guidance Note 3 or Table I1 in the On-Site Guide.
Using Tables for Verification
- Cable Specifications: 6mm² (line) by 2.5mm² (CPC) twin and earth.
- Resistance Calculation: Combined resistance for 6x2.5 copper cable: 10.499 milliohms per meter.
- Formula:
- Total resistance = milliohms per meter x cable length.
- Calculate length if resistance is known.
- Expected Results:
- 19m should return a low ohms reading of 0.2 ohms.
- Resistance for line to neutral: 6.16 milliohms per meter for both 6mm² line and neutral.
- Line and neutral calculated resistance for 19m: 0.117 ohms.
Faulty Circuit Diagnosis
- Scenario: RCD or MCB tripping, indicating potential faults.
- Fault Indicators:
- Line to Earth faults may trip RCD.
- Line to Neutral faults may trip MCB.
- Example Fault: Nail piercing the cable about halfway, creating an earth fault.
Fault Isolation
- Method: Test with two conductors at a time.
- Comparison:
- Line to Neutral and Neutral to CPC readings may resemble healthy circuit.
- Line to CPC shows abnormal reading indicating fault.
Locating Faults
- Method: Use resistance values and Table B1 or I1 to calculate distance to the fault.
- Example Calculation: Fault located approximately 9.5m from the consumer unit.
Recap & Best Practices
- Formula Variants: For resistance or length calculations based on known data.
- Tables Usage: Familiarize with on-site guide and guidance note tables.
- Testing Tips:
- Use connectors for return paths.
- Test between two conductors to isolate faults.
- Record test results; avoid relying solely on memory.
Conclusion
- Understanding and practicing with tables and formulas is crucial for accurate fault diagnosis and circuit testing.
Thank you for watching the video and remember to subscribe for more educational content on electrical circuits.