Purpose
Measure the temperature and humidity across the entire warehouse
Record readings of various points simultaneously and continuously
Duration
Minimum of 7 days
Maximum of 14 days
Method
Data Logger Placement
Place data loggers at equal distances across the warehouse based on calculations
Can be placed in both existing and new warehouses
Types of Tests
Empty Test
Conducted in a new warehouse without any load
Analyze readings for a couple of days
Loaded Test
Analyze readings under normal loaded conditions (at least 50% load)
Warehouse should be loaded to normal usage patterns (e.g., 60%)
Full Load Test
Conducted with 90-100% load
Use dummy loads if needed to achieve 100% capacity
Data Recording
Download data from loggers upon completion
Upload to mapping study software
Software generates results
Analysis
Temperature and humidity analyzed separately
Recommended humidity level: below 65% RH for medicine storage
Equipment
Standard data loggers or wireless real-time data loggers
Wireless real-time loggers allow for remote data monitoring
Reporting
Summary graphs for all tests (empty, loaded, door opening, startup, power failure)
Includes maximum and minimum temperature, duration of excursions, etc.
Report comprises risk analysis, recommendations, and details of each test
Qualification report includes equipment details and calibration reports
Summary & Recommendations
Summarize test results
Identify hot and cold points
Recommend positions for recording instruments